Wednesday 8 September 2010

Generator testing using AC load banks


Regular maintenance
Wet stacking occurs predominantly with under loaded gen-sets that are used in prime power applications. By using a load bank, as part of any regular maintenance routine, will provide the generators an essential health check and prevent diesel engine failure due to wet stacking. 


Wet stacking
Wet stacking occurs due to the lightly loading ( at levels of less than 35% for a prolong time period ) of a genset.   The consequence of low loading results in wet un-burned fuel deposits building up in the engine cylinders. This fuel residue over time will line the combustion chamber cylinders and cause a reduction of the engines performance rating and efficiency which will ultimately cause premature failure of the generator. 



As part of the regular maintenance it is recommended that the genset is loaded in incremental steps with due consideration of the age and service history of the genset is given prior to  loading at 100%


Running the generator on loads above 35% of the genset rating will allow the engine to reach the recommend operating temperature, which will burn off the choke deposits. 


Load bank generator service
Hillstone Products can provide the complete genset load banking package.  Our load bank team(s) operate across the whole of the UK and the supplied service frequently involves:


  •                Off loading of the load bank
  •                Positioning of the load bank with safety barriers as required
  •                Laying cables without causing obstruction
  •               Operating load bank  
  •                Removal of equipment from site
We are happy to work along side customer's service teams or on behalf of customers as required.


The available range of load banks allows for testing of gensets up-to 2000KVA.
Our sales team are available to discuss your Genset testing requirements:

www.hillstone.co.uk    Tel +44(0) 161 763 3100    sales@hillstone.co.uk 

Saturday 4 September 2010

19" rack data center HVAC load banks

Within a server room installation and commissioning of HVAC, the use of dedicated 19" rack load banks are used as server simulators to provide heat exchange testing conditions.  This allows for verification of HVAC design and performance of cold & hot aisles.




The power consumption of server rooms typically can range from 90KW to more than 2000KW.  The use of load banks for HVAC testing by virtue that they are connected into the power infrastructure therefore allow verification of  the electrical wiring & balance of the PDU and also as part of black start testing of the standby power UPS & generator systems. 


Fitting the load banks into the racks prove to potential customers the electrical supply is ready to have the very expensive servers installed and switched on.


The typical ratings of single phase 19" load banks include 2KW, 3KW, 4KW and 6KW, allowing for connection to 16A - C19 sockets or 32A - IEC309 / BS4343 commando plugs.


Alternative solutions include the use of 24KW aisle load banks that provide 6 x 4KW load channels that are directly connected via 32A - IEC309 / BS4343 commando plugs to the under floor or ceiling mounted supply points within the data rooms.



Once the load banks are fitted it is also important to install blanking plates to seal off the racks to create  realistic thermal conditions.


Hillstone provides a complete service of load bank rental supply and installation.  We work closely with the customer to ensure the loads are installed balanced across the PDU and connected under the floor or up to ceiling power points.


Our sales team are available to discuss your HVAC testing requirement:
www.hillstone.co.uk    Tel +44(0) 161 763 3100    sales@hillstone.co.uk 

DC hire load banks

When choosing your DC load bank rental partner, your list of requirements will include:
  • Complete technical understanding of  your requirement
  • Availability of equipment
  • Reliable logistics for both delivery and collection
  • Support and backup 
For 20 years Hillstone Products, a UK manufacturer and rental company for load banks, have invested and developed the largest DC fleet of rental load banks in the UK and the Middle East - from Dubai UAE.
Our technical sales team take great pride with every enquiry to ensure that the selected equipment is fully compatible with the battery, charger or fuel cell to be tested. 


The DC load bank range are available  from 12V to 600V,  allowing discharge testing from 50A to over 1000A.  This can be achieved by using multiple portable units in parallel.  


The DC load banks are very portable and allow for ease of movement to the battery or UPS room that can be carried by one man.


The Hillstone web site hosts operating manuals for the majority of the hire fleet load banks.


A summary of the complete hire fleet range is available online at: http://www.hillstone.co.uk/hire/index.html


www.hillstone.co.uk    Tel +44(0) 161 763 3100    sales@hillstone.co.uk